Kestvan transposed aluminium conductor
Kestvan supplies transposed aluminium conductors to customer drawings for transformer and reactor windings. Specify the strand position sequence, transposition pitch or repeat length, and finished cross-section. Reference constructions include seven-wire bundles and layered arrangements.
Request a conductor quotationTransposed aluminium conductor quotes and samples About Kestvan

Reference specification ranges
| Construction | Strand count | Individual wire diameter (mm) | Finished height (mm) | Finished width (mm) | Stack count |
|---|---|---|---|---|---|
| Transposed conductor with seven-wire bundles | 7 per bundle | — | — | — | — |
| Double-layer transposed conductor | 2×3–2×20 | 0.8–5.2 | 3.8–9.3 | 8–52 | — |
| Combined double-layer transposed conductor | — | 0.8–5.2 | 8–28 | 8–52 | ≤4 |
Values describe reference configurations. Confirm the specified combination against the project drawing, as the range limits may not be available together. A dash indicates a value that was not specified.
Conductor construction
A transposition schedule moves strands through defined positions along the length. An option with seven wires per bundle, double layer or combined double-layer construction can be reviewed against the required layout and repeat length.
Use this option for transformer or reactor coils whose electrical design specifies strand transposition. Include the operating current and frequency profile, conductor cross-section and lead arrangement for technical review.
Specification and acceptance requirements
| Parameter | What to specify |
|---|---|
| Strand and layer configuration | Specify the seven-wire bundle option or the double-layer or combined double-layer arrangement, aluminium grade and strand dimensions in mm. |
| Pitch and sequence | Set the transposition pitch or repeat length in mm, position sequence and end positions. |
| Finished profile and tolerance | Set the final width and height or diameter in mm and tolerances at the transposition zones. |
| Insulation and electrical tests | Define strand insulation and wrapping, maximum DC resistance in Ω/km at the stated temperature and strand isolation checks. |
| Bending, joints and reels | Specify bend direction and minimum radius, permitted joints, continuous length in m and the reel drawing. |
Send the winding drawing and service conditions. The quotation confirms the available construction, aluminium grade, dimensions, insulation, inspection limits and reel requirements for the project.
Material data and inspectionTransposed aluminium conductor quotes and samples
Transposed aluminium conductor RFQ worksheet
Open the CSV in Excel and fill in the blank column from your winding drawing. Use these details in your enquiry to Kestvan. Sample availability, final dimensions and inspection scope are confirmed for each order.
- Transformer or reactor application, winding drawing and aluminium grade
- Bare and finished dimensions, cross-section and tolerances
- Strand count and dimensions, stranding lay length or transposition pitch and sequence
- Individual strand insulation, outer wrap or resin system and thermal requirements
- Maximum DC resistance at the stated reference temperature, required tests and acceptance limits
- Quantity, continuous length per reel, reel dimensions and packing requirements
Enter the drawing number and revision with your enquiry. For a trial sample, include the requested length, dimensional tolerances, insulation and any DC resistance acceptance limit at the specified temperature. Sample availability and test scope are confirmed for each project.
Comparing DC resistance in conductor sample reports
These illustrative readings use the same complete-conductor connection and a measured temperature of 20 °C. Divide resistance in milliohms by gauge length in metres to obtain ohms per kilometre.
- 5.60 mΩ ÷ 10.0 m = 0.560 Ω/km
- 14.0 mΩ ÷ 25.0 m = 0.560 Ω/km
Record the sample ID, drawing revision, measured temperature and length between voltage taps. Identify the strands connected for the measurement and whether the test covered one strand or the whole conductor. Compare against the project limit using the agreed test connection and temperature correction.
IEC 60851-5 Test 5 covers electrical resistance of winding wire. The project specification determines the applicable test method and edition. IEC 60851-5:2026
Mingyu Ma, Sales Manager at Kestvan, handles winding conductor enquiries. He coordinates drawings, sample requirements and the information needed for a quotation.
Discuss conductor requirementsProduct selection and enquiry
When to use this product
The winding drawing determines the strand-position changes and end arrangement of a transposed aluminium conductor. Check the finished dimensions through the transposition zones for coil fit.
What to send for a quotation
Send the current drawing revision and state the strand insulation and permitted joints. For electrical acceptance, give the reference temperature and identify whether the DC resistance limit applies to a strand or the whole conductor.
From the winding drawing to reel acceptance
Kestvan supplies transposed aluminium conductors for transformer and reactor windings to customer drawings. Use the winding drawing to review the conductor construction, then carry its revision through the quotation, sample and reel acceptance records.
Check the construction against the drawing
Read the ranges for the selected construction separately. Check the strand arrangement and finished dimensions together against the winding drawing.
Reference ranges by construction
Keep sample and drawing references on the enquiry
Enter the approved drawing revision and selected construction in the enquiry. Include a traceable sample ID when a sample is available.
Transposed aluminium conductor enquiry worksheet
Match the reel record to the agreed acceptance criteria
On receipt, match the reel or batch ID and the drawing revision. Check the measured complete-conductor DC resistance together with the test connection and temperature against the agreed criterion. The illustrative calculation shows how to interpret a result.
Agree what to check before using the first reel
| Decision | What to verify |
|---|---|
| Position cycle and reel ends | Identify the released drawing revision. Show the position sequence and specify whether the stated length is one transposition step or a full cycle. Mark strand identification and orientation at both ends. |
| Finished section at the winding | Agree where to measure the insulated profile, including at transposition zones, and how to check it against the available winding space and bend limits. |
| Reel acceptance record | Agree how resistance is measured, whether the limit applies to a strand or the full conductor, the reference temperature, how permitted joints are recorded and the minimum continuous length per reel. |